Required Documents:
Two sets of paper plans and two sets of equip specs must be submitted. All plans shall bedrawn to scale, said scale shall be 1/8” or greater. Upon review one set of plans and specs shall be returned. One shall be retained by the fire dept. If additional sets are desired, contractor shall provide them.
A stamped set of drawings and specs must remain on the job site until final inspection is performed by MCFD. State issued company license shall be provided. License holder and number shall be provided. Provide description of scope of work to be performed
Shop Drawings:
Submitted plans shall comply with the requirements of chapter22 of NFPA 13 (2007 Edition) with room names and ceiling/roof heights not shownin full height elevation. Flow tests shall be witnessed by MCFD and scheduled 48 hrs in advance. Mains shall not passwithin 5 feet horizontally of electrical panels.
Fees:
For all systems fee$50.00, plus .01 cents per foot for new systems.
$50.00 flat and feefor all work done as remodel or retro.